Modbus RTU TPMS - Register Map and Polling Example

· 8 min read

The single most important sentence

The receiver is a Modbus RTU slave. It answers; it does not push.

That one sentence decides the whole integration. Your PLC or controller is the master: it decides when

to ask, how often to ask, and what to do with a missing answer. If you design as if the receiver will

"send when something changes", you will build a system that looks dead and blames the hardware.

Everything else on this page follows from that.

What the interface actually is

The receiver is built with one interface per unit, fixed at the factory — Modbus RTU is one of the

options (the same hardware is also built as CAN, RS232 or RS485). It is not four interfaces at once, and

it cannot be reconfigured in the field to be a different one. So "Modbus RTU" appears on the order, not in

a settings menu.

Physically Modbus RTU runs on RS485 in most installations: two wires plus a reference, multi-drop along

the machine. Three details decide whether it is reliable, and none of them is in the protocol:

  • termination at the physical ends of the segment;
  • bias so an idle line sits at a defined level;
  • ground reference shared by all nodes, because a floating reference is how "it works on the bench"

becomes "it drops frames in the cabinet".

How the register map is organised (and why we do not publish a generic one)

A TPMS receiver has to present, per wheel position, at least pressure and temperature, plus status

information: which positions are heard, which sensor IDs are bound, battery condition, and the age of the

last reading. How those are packed into 16-bit registers is a design decision, and it differs with the

configuration — how many wheel positions are enabled, whether the frame carries raw sensor IDs, whether

temperatures are signed.

So the register map is supplied with the unit, per project. What this page can do is tell you how to

prepare for it, and what to check when it arrives.

When the map arrives, read these five things first:

#What to look forWhy
1Register type — holding vs input registersDecides whether you use function 03 or 04
2Word order for 32-bit valuesA pressure packed as two registers can be either order; getting it wrong gives a plausible wrong number
3Scaling factor per valueRaw counts × 0.1 kPa is not the same as × 1 kPa; a missing factor looks like a calibration error
4Signed vs unsigned temperatureSub-zero temperatures become 65000-ish values if you treat them as unsigned
5Which positions come firstThe mapping from register index to wheel position is the thing your maintenance team will live with

That last one is worth dwelling on. A mapping that is technically correct but does not match the way the

machine is described ("front left, inside rear, third axle") will be misread by a human under time

pressure. Ask for the map to be expressed in your axle/position convention, not in "index 0..N".

A polling example (shape, not addresses)

A typical read is a single request for a block of registers, then a fixed layout on the response. In

pseudocode:

```

every 2 s:

request = slave_id, function 03, start_register, register_count

response = send(request) with timeout 300 ms

if no response:

retries += 1; if retries > 2: mark link down; continue

parse response as map describes (word order, scale, sign)

for each enabled position:

update pressure, temperature, last_seen

```

Three notes on that shape:

Poll slower than the data changes. The receiver publishes on a 500 ms cycle on the output side, so

polling at 100 ms does not give you fresher data — it gives you four identical answers and more bus

traffic. Two seconds is usually enough for a tyre-pressure decision, and it leaves headroom for other

nodes on the same segment.

Keep a last_seen per position. A position that stops appearing is a finding, not a gap. The receiver

can only report what it hears; if a sensor goes quiet or a radio path closes, the register simply stops

updating. Without last_seen, that looks like "a tyre at a stable pressure", which is the one wrong answer

you must not give.

Timeout is a state, not an error. A missing reply should set a link state (and eventually an alarm of

its own), not throw an exception that stops the scan. Bus faults are transient; a scan loop that dies on

the first timeout will be found dead days later.

Alarm logic: the part that decides whether people trust the system

Two rules, learned the hard way on vehicles and machines:

Do not alarm on a single sample. Alarm when a value is out of band for N consecutive polls, or when

it is still moving in the wrong direction on the next poll. One sample is noise; a trend is information.

Separate "low pressure" from "no data". They are different failures with different actions: a low

tyre needs the vehicle stopped; a silent position needs someone to look at a sensor or a radio path.

Merging them into one "tyre fault" alarm trains the operator to ignore both.

If you want a third state, the useful one is "sensor heard but not yet bound to a position" — that is

what you see during commissioning, and it is much better to see it on a screen than to wonder why one

wheel is missing.

What to send us to close the loop

Four things, and we answer in writing before anything ships:

1. Master model and polling rate — the PLC or controller, and how often you want to read.

2. Wheel positions and their naming — how your team describes positions, so the map matches it.

3. Existing segment — how many nodes, cable length, termination and bias already in place.

4. Alarm policy — thresholds, how many samples before an alarm, and what a "no data" position should do.

With those, the integration is a configuration exercise rather than a debugging one. Modbus is an old,

well-understood protocol; almost every Modbus integration failure in this application is a mismatch in

those four items, not in the protocol.